An eye of Insurance THERMAL GRAPHICS We are located in the delaware valley serving NJ, DE, PA, MD |
|
SAMPLE REPORT
THERMAL
GRAPHICS INSPECTION FINDINGS
Thermal Image Visual Image EQUIPMENT INFORMATION: 3 Phase transformer bank Main Service. Location: Pole # 1234 COMMENTS OF THEROGRAPHER AND/OR ELECTRICIAN:This is serious and needs to be replaced (ASAP) before an unexpected shutdown SUSPECTED NATURE OF PROBLEM: Loose and/or deteriorated bushing on the transformer or overloaded Maintenance to consider: Tightening lugs/replace bushings check for an unbalanced PhaseHISTORY: (if any) EST. COST OF UNEXPECTED FAILURE: This is estimated by the customers plants Engineer Criticality: Serious - repair in immediate future! Thermal Graphics 665 Greenwood ave, Pennsvlle, NJ 08070-2646 (609) 935-1434
|